Features
- Corrosion Resistant Brass Construction
- 1-1/2” swivel inlet X 1-1/2”male outlet
- Eductor rated for optimum flow at 200 PSI (14 Bar)
- Furnished with 30”(76cm) pick up tube
- Variable metering valve
- Removable metering valve
- A large, easy to read metering dial
- Ball check valve prevents back flow into foam concentrate
Operating Procedures
- Must be used with a nozzle of equivalent flow rate
- Maximum hose lay between eductor and nozzle on level ground using 1½"(3.8 cm) hose is 150 ft.(46m)
- Maximum hose lay between eductor and nozzle on level ground using 2"(5 cm) hose is 300 ft.(91m)
- Normal inlet operating pressure at eductor is 200 psi; however, the eductor can be used at lower inlet pressures with a corresponding reduction in flow rates
* Pressure loss through the Chemguard eductor is approximately 35% of the inlet pressure
Suitable
- Suitable for use with water, AFFF, AR-AFFF, Fluoroprotein and Class “A” foam concentrates
Part No:
|
Description(lpm)
|
Material
|
Inlet
|
Weight(kg)
|
Proportioning Metering Valve
|
CES60
|
60 GPM(227)
|
Brass
|
1.5” NST
|
10 LBS.(4.5)
|
.5%,1%,3%,6%
|
CES60NPSH
|
60 GPM(227)
|
Brass
|
1.5” NPSH
|
10 LBS.(4.5)
|
.5%,1%,3%,6%
|
Part No:
|
Description
|
CE95T
|
Pick Up Tube
|
MV60
|
Metering Valve for 60 GPM(227 lpm) Eductor
|
MV95
|
Metering Valve for 95 GPM(360 lpm) Eductor
|
PTE
|
Pick Up Hose and Tube w/Clamps
|
|
|